Programming D-95
DC590+ DRV Series DC Digital Drive
PRESET SPEEDS
Parameter Tag Range
LIMIT 600 FALSE / TRUE
Clamp output to MAX SPEED if TRUE.
GRAY SCALE 610 FALSE / TRUE
Selects Gray Scale encoding when TRUE, Binary encoding when FALSE. When gray scale is selected, only one input changes between state
preventing the mis-selection of intermediate states.
INPUT 0 to INPUT 7 564, 565, 566, 567, 568, 569, 570, 571 -3000.0 to 3000.0
Pre-set input variables.
PRESET O/P 572
.xx %
Scales the selected preset input by MAX SPEED.
OUTPUT FPM 593
.x
Outputs the selected INPUT value.
Functional Description
INPUT 0
INPUT 1
INPUT 3
SELECT 1
SELECT 2
SELECT 3
INVERT O/P
INPUT 4
INPUT 5
INPUT 6
INPUT 7
INPUT 2
OUTPUT
100%
MAX SPEED
PRESET OP %