Technical Specifications E-1
DC590+ DRV Series DC Digital Drive
Technical Specifications
Environmental Details
Frame 1 : 0°C to +45°C (32°F to 113°F)
Frame 2 : 0°C to +45°C (32°F to 113°F)
Frame 3 : 0°C to +45°C (32°F to 113°F)
Frame 4 : 0°C to +40°C (32°F to 104°F)*
Frame 5 : 0°C to +40°C (32°F to 104°F)*
Frame 6 : 0°C to +40°C (32°F to 104°F)*
Frame 7 :
0°C to +40°C (32°F to 104°F)*
Operating Temperature
* Can be enclosed in a 40°C (104°F) ambient when using the external vent kit supplied with the drive.
Operating temperature is defined as the ambient temperature to the immediate surround of the drive, when the drive and other equipment
adjacent to it is operating at worst case conditions.
Output current values should be derated at 1% per degree Centigrade above rated temperature up to a maximum of 55°C (126°F).
Storage Temperature -25°C to +55°C (-13°F to 126°F)
Shipping Temperature
-25°C to +70 °C (-13°F to 158°F)
Product Enclosure Rating
IP00 (Europe) [Frame 1 unit is IP20]
UL Open Type (North America/Canada)
If the product enclosure is totally enclosed, the exposed metal surface dissipates approximately 50W/m² for a 10°C temperature rise of internal
air above ambient.
Altitude
If >500 metres (1650 feet) above sea level, derate Motor Power rating by 1% per 200 metres (660 feet) to a maximum of 2,000 metres (6,561
feet)
Humidity
Maximum 85% relative humidity at 40°C non-condensing
Atmosphere Non flammable, non corrosive and dust free
Vibration Test Fc of EN60068-2-6
10Hz<=f<=57Hz sinusoidal 0.075mm amplitude
57Hz<=f<=150Hz sinusoidal 1g
10 sweep cycles per axis on each of three mutually perpendicular axis
Climatic Conditions Class 3k3, as defined by EN60721-3-3 (1995)
Safety
Europe EN61800-5 : 2003, when fitted inside an enclosure
North America/Canada
UL508C
Overvoltage Category Overvoltage Category III (3-phase supply), Overvoltage Category II (auxiliary supply)
Pollution Degree Pollution Degree 2