EasyManua.ls Logo

Parker 590+ DRV - Page 528

Parker 590+ DRV
544 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E-22 Technical Specifications
DC590+ DRV Series DC Digital Drive
Terminal Information - Option Boards
Terminal Description Terminal Function Signal Level Terminal Number
RCV-
RCV+
Serial Communications Port P1 Receive Terminals
Balance Line Receiver input compatible with RS422 signal levels
H5
H6
PROFIBUS
0Vext
+5VDCext
Signal reference for Profibus
+5VDCext/50mA supply for Profibus
H1
H2
B-B`
A-A`
Receive/Transmit-Data-P
Receive/Transmit-Data-N
H3
H4
RTS
0Vext
For connecting repeater
As pin 1
H5
H6
Wiring Requirements for EMC Compliance
Where shielded/armoured cables are specified, use "SY" or "CY" type cables for better performance.
Model Power Supply Cable Motor Cable External Filter to Converter Cable Signal/Control Cable
Cable Type
(for EMC
Compliance)
Unscreened
Screened/
armoured
Replace flying leads with
screened/armoured when >0.6m
Screened
Segregation
From all other wiring
(clean)
From all other wiring (noisy) From all other wiring (sensitive)
Length Limitations
With External Filter
Unlimited 50 metres
As short as possible
25 metres
Screen to Ground
Connection
Both ends
Both ends
Converter end only