E-24 Technical Specifications
DC590+ DRV Series DC Digital Drive
Wire Sizes and Termination Tightening Torques (Frames 1, 2, 3, 4 & 5)
• Control wiring must have a minimum cross-section area of 0.75mm
2
(18AWG)
UL EUROPE
Terminations
Maximum Tightening
Torque
Recommended Wire Size Maximum Terminal Aperture Size (AWG) Maximum Terminal Aperture Size (mm
2
)
Frame 2
40A UNITS
A+, A- 5.6Nm (50 lb-in) 8 AWG 2/0 70
L1, L2, L3 5.6Nm (50 lb-in) 8 AWG 2/0 70
Grounding terminal 5.6Nm (50 lb-in) 6 AWG 2/0 70
AUX. CONT. (TB4) 0.5Nm (5.0 lb-in) 12 AWG 12 2.5
FL1, FL2, F+, F- 0.8Nm (7.0 lb-in) 14 AWG 12 2.5
BL1, BL2, BL3 0.8Nm (7.0 lb-in) 6-18 AWG * 12 2.5
L, N, 3, 4, TH1, TH2 0.5Nm (5.0 lb-in) 12 AWG 12 2.5
70A UNITS
A+, A- 5.6Nm (50 lb-in) 3 AWG 2/0 70
L1, L2, L3 5.6Nm (50 lb-in) 6 AWG 2/0 70
Grounding terminal 5.6Nm (50 lb-in) 6 AWG 2/0 70
AUX. CONT. (TB4) 0.5Nm (5.0 lb-in) 12 AWG 12 2.5
FL1, FL2, F+, F- 0.8Nm (7.0 lb-in) 14 AWG 12 2.5
BL1, BL2, BL3 0.8Nm (7.0 lb-in) 6-18 AWG * 12 2.5
L, N, 3, 4, TH1, TH2 0.5Nm (5.0 lb-in) 12 AWG 12 2.5
110A UNITS
A+, A- 5.6Nm (50 lb-in) 1/0 AWG 2/0 70
L1, L2, L3 5.6Nm (50 lb-in) 3 AWG 2/0 70
Grounding terminal 5.6Nm (50 lb-in) 6 AWG 2/0 70
AUX. CONT. (TB4) 0.5Nm (5.0 lb-in) 12 AWG 12 2.5
FL1, FL2, F+, F- 0.8Nm (7.0 lb-in) 14 AWG 12 2.5
BL1, BL2, BL3 0.8Nm (7.0 lb-in) 6-18 AWG * 12 2.5
L, N, 3, 4, TH1, TH2 0.5Nm (5.0 lb-in) 12 AWG 12 2.5
165A UNITS
A+, A- 42.4Nm (375 lb-in) 4/0 AWG 250 cmil 120
Power cables must have a minimum rating of 1.1 x full load current - EUROPE