4.5 Parameter settings
General
There are two levels of protection for parameters:
a) Direct (D): with immediate access, User-changeable;
b) Password protected (U): password required for access, (do not change).
4.5.1 Chiller parameters (&IJ)
PARAMETER CODE TYPE DEFAULT
Unit of measurement.
Ai
D
OFF
Alarm relay management
CFJ1
D
0
Restore default parameters
dEF
D
OFF
Remote on / off enabling
A7
D
0
Software version
L8HU
D
1.69
Unit adress
CF30
D
1
Baud rate
CF31
D
3
Modbus protocol
CF32
D
1
Supervisor on / off enabling
SUP
D
OFF
Dinamic set point eanbling
Erd
D
OFF
4.5.2 Temperature control (&PS)
PARAMETER CODE TYPE DEFAULT
Temperature control set point (standard)
SEt
D
13.0
Temperature “precision control” set point (standard)
SEt
D
20.0
Temperature control differential (NOT present in confi gura-
tion “precision control”)
dIFI
D
4.0
4.5.3 Maintenance parameters (0QW)
PARAMETER CODE TYPE DEFAULT
Unit working hours
UH
D
-
Unit working hours (X1000)
UHL
D
-
Unit partial working hours
UPH
D
-
Unit partial working hours (X1000)
UPHL
D
-
Compressor working hours 1
C1H
D
-
Compressor working hours 1 (x1000)
C1HL
D
-
4.5.4 Probe parameters (%7, %7)
Probe (%7)
PARAMETER CODE TYPE DEFAULT
High temperature alarm (water)
HA1
D
60
Probe (%7)
PARAMETER CODE TYPE DEFAULT
High temperature alarm (water)
HA2
D
60
4.5.5 Alarm history ($/+L)
PARAMETER CODE TYPE DEFAULT
Alarm number
+<63
D
-
See alarm code
+<6&
D
-
See day and month of the alarm
+<6G
D
-
See hour and minutes of the alarm
+<6W
D
-
bt1 temperature at time of the alarm
+<6
D
-
bt2 temperature at time of the alarm
+<6
D
-
SET conditions at time of the alarm
+<6
D
-