43
This screen is the SENSOR2: SETUP setup start screen. To go
to the SN2: TYPE setup screen, press SET.
n/a n/a
To go to the SN2: TYPE setup screen, press SET. n/a n/a
To set a sensor type for Sn2, select A99, NTC, or NON (none)
and press SET.
• A99
• NTC
• NON
A99
To go to the SN2: OFFSET setup screen, press SET. n/a n/a
To set the offset value for Sn2, select the offset value from the
range -2.5°C to 2.5°C (-5°F to 5°F) and press SET.
-2.5°C to 2.5°C
(-5°F to 5°F)
0° (C)
0° (F)
This screen is the EVAP FAN TYPE setup start screen. To go to
the EVAP FAN TYPE setup screen, press SET.
n/a n/a
To set a motor for the evaporator fan, select 1-SPD (single-
speed) or 2-SPD (two-speed) EC motor fan and press SET.
• 1-SPD
• 2-SPD
1-SPD
This screen is the DEFROST TYPE setup start screen. To go to
the DEFROST TYPE setup screen, press SET.
n/a n/a
To set the defrost type, select OFF/CYC (off-cycle), HOT/GAS
(hot gas) or ELC/TRC (electric resistive heat) and press SET.
• OFF/CYC
• HOT/GAS
• ELC/TRC
OFF/CYC
This screen is the DEFROST TERM TYPE setup start screen.
To go to the DEFROST TERM TYPE
setup screen, press SET.
Note: The DEFROST TERM TYPE screens do not display if
the defrost type is OFF/CYC, because off-cycle defrost
termination is time-based.
n/a n/a
To set a defrost termination type, select TI/ME (time-based
termination), HV/BIN (high-voltage binary temperature switch),
or TE/MP (temperature-based termination) and press SET.
• TI/ME
• HV/BIN
• TE/MP
TI/ME
Table 15: A5xx Controller screens (Part 5 of 15)
Screen name in
message field
Parameter description, behavior, or user action Value range or
selection list
Default
value or