33
Setting up the defrost setup screens
To set up the defrost setup parameters, see the following section, Setting up the defrost schedule, and Setting up
adaptive defrost.
Setting up the defrost cycle
To set up the defrost cycle, navigate to the DEFROST SETUP start screen and press SET. To move through the
DEFROST SETUP screens, press the DOWN and UP arrow keys.
To set the maximum defrost duration time, select the maximum defrost
duration value from the range 0 minutes to 99 minutes and press SET.
Note: All defrost cycles, regardless of their termination type, terminate
when the system reaches the maximum defrost duration value.
To set the drip time delay, select the drip time delay value from the range
0 minutes to 10 minutes and press SET.
To set the defrost termination temperature, select the defrost termination
temperature value from the range 30°F to 90°F and press SET.
To set the evaporator fan delay time, select the delay time value from the
range 0 minutes to 15 minutes and press SET.
To set the defrost schedule type, select SCHEDU (scheduled) or ADAPTI
(adaptive) and press SET.
15°FA52x
DEFROST
DURATION
SET
DEFROST TERM
TEMPERATURE
SET
90
30
DEFROST
DURATION
30 MIN
EVAP FAN
DELAY TIME
1 MIN
SET
F
10°
SET
SET
SET
SET
EVAP FAN
DELAY TIME
SET
DEFROST SETUP
SET
DRIP TIME
SET
DRIP TIME
5 MIN
SET
DEFROST TERM
TEMPERATURE
40°
35
20
DEFROST
SCHEDULE
ADA
PTI
SET
DEFROST
SCHEDULE TYPE
SET