To set the maximum defrost duration time, select the maximum defrost
duration value from the range 0 minutes to 99 minutes and press SET.
Note: All defrost cycles, regardless of their termination type, terminate
when the system reaches the maximum defrost duration value.
To set the drip time delay, select the drip time delay value from the range
0 minutes to 10 minutes and press SET.
To set the defrost termination temperature, select the defrost termination
temperature value from the range 30°F to 90°F and press SET.
To set the evaporator fan delay time, select the delay time value from the
range 0 minutes to 15 minutes and press SET.
To set the defrost schedule type, select SCHEDU (scheduled) or ADAPTI
(adaptive) and press SET.