Installer Manual Autotrol 368 / 604-606 - Programming
Ref. MKT-IM-007 / A - 16.12.2016 29 / 54
6.3. Time clock regeneration (604 only)
Set the time between each regeneration.
6.4. Volumetric regeneration (606 only)
Set the capacity in [m
3
] between each regeneration.
6.5. Calendar override setting (606 only)
The 606 controller needs a method to set days between regeneration for regulatory requirements and
in cases when the flow sensor has failed.
A Press until desired interval appears then release.
→ Range from 0 through 30;
0 = Disabled;
0.3 = Regeneration every 8 hours : at 2, 10 and 18 hours;
0.5 = Regeneration every 12 hours : at 2 and 14 hours;
1 - 30 = Regeneration every X days (every 3 days in this
example).
A Press until desired capacity appears then release.
→ Range from 0.4 to 9.5 m
3
;
from 0.4 m
3
to 1.0 m
3
by increments of 0.05 m
3
(12 increments);
from 1.0 m
3
to 3.0 m
3
by increments of 0.1 m
3
(20 increments);
from 3.0 m
3
to 5.0 m
3
by increments of 0.2 m
3
(10 increments);
from 5.0 m
3
to 9.5 m
3
by increments of 0.5 m
3
(10 increments).
A Press and hold and for 3 seconds.
→ The programmed calendar override is displayed.
B Press to increases value.
→ Range from 0 through 30;
0 = Disabled;
0.3 = Regeneration every 8 hours : at 2, 10 and 18 hours;
0.5 = Regeneration every 12 hours : at 2 and 14 hours;
1 - 30 = Regeneration every X days (every 3 days in this
example).