Installer manual Fleck 9100 SXT - Description
14 / 108 Ref. MKT-IM-004 / E - 06.10.2020
3 Description
3.1 Technical specifications
Design specifications/ratings
Valve body PPO (Polyphenylene oxide)
Rubber components EP or EPDM
Valve material certification DM174, ACS
Weight (valve with controller) 3kg(max)
Recommended operating pressure 1.8 - 8.6bar
Maximum inlet pressure 8.6bar
Hydrostatic test pressure 20bar
Water temperature 1 - 43°C
Ambient temperature 5 -40°C
Flow rates (3.5bar inlet - valve only)
¾" 1"
Continuous service flow (Δp=1bar) 4m
3
/h 4.5m
3
/h
Peak service flow (Δp=1.8bar) 5.4m
3
/h 5.9m
3
/h
Cv* 4.8gpm 5.2gpm
Kv* 4m
3
/h 4.5m
3
/h
Maximum backwash flow
(Δp=1.8bar)
1.9 m
3
/h 1.9 m
3
/h
*Cv: Flow rate in gpm across the valve at a pressure drop of 1 psi at 60°F.
*Kv: Flow rate in m
3
/h across the valve at a pressure drop of 1 bar at 16°C.
Valve connections
Tank Thread 2½" - 8NPSM
Inlet/Outlet ¾" or 1"BSP, male
Riser tube 26.7mm O.D., 1.05"tube
Drain line ½"O.D.
Brine line (1600/1610) ⅜"
Electrical
Transformer input voltage 230VAC
Input supply frequency 50 or 60Hz
Transformer output voltage 24VAC
Motor input voltage 24VAC
Controller input voltage 24 VAC
Controller max. power consumption 8 W