Pentair intellidrive pid10 - User Manual

Pentair intellidrive pid10
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
6714 1112
PID10, PID20, PID30, PID50
OWNER’S MANUAL
PENTEK INTELLIDRIVE
NOTICE D’UTILISATION
PENTEK INTELLIDRIVE
MC
MANUAL DEL USUARIO
PENTEK INTELLIDRIVE
Installation/Operation/Parts
For further operating,
installation, or maintenance
assistance:
Call 866-9 PENTEK
(866-973-6835)
English ................... Pages 2-23
Installation/Fonctionnement/Pièces
Pour plus de renseignements
concernant l’utilisation,
l’installation ou l’entretien,
Composer le (866) 9 PENTEK
(866-973-6835)
Français .............. Pages 24-45
Instalación/Operación/Piezas
Para mayor información sobre
el funcionamiento, instalación o
mantenimiento de la bomba:
Llame al 866-9 PENTEK
(866-973-6835)
Español .............. Paginas 46-67
© 2015 Pentair, Inc. All Rights Reserved. PN957 (04/10/15)
293 WRIGHT STREET, DELAVAN, WI 53115 WWW.PumPS.COm
PH: 1-866-9 PENTEk

Questions and Answers

  • F
    Frank MartinezAug 20, 2025
    Why is my Pentair Controller showing an Over Voltage error?
    • L
      lthomasAug 20, 2025
      If the Pentair Controller displays an 'Over Voltage' error, it could be due to several reasons. First, there might be an internal drive short, which you can check by measuring the outputs with an ohmmeter while the power to the drive is off. Second, power cycling on and off could be the issue, so check for a generator or switching on the input line. Finally, high line voltage could be the cause; measure the incoming line voltage to the drive, ensuring it's between 190V and 265V.
  • R
    ryan35Aug 22, 2025
    How to fix Over Current error on Pentair intellidrive pid10 Controller?
    • J
      James DicksonAug 22, 2025
      If your Pentair Controller displays an 'Over Current' error, it typically indicates a shorted output. Check the motor cables for any shorts. It could also be due to damaged wire insulation. Inspect the motor wire insulation using a megger.
  • J
    Jennifer MooreAug 25, 2025
    What to do if Pentair intellidrive pid10 Controller cannot start the motor?
    • S
      Stephanie KellerAug 25, 2025
      If your Pentair Controller isn't starting the motor, first ensure that the Service Factor Amps value entered is correct. A missing or incorrect Service Factor Amps value can prevent the motor from starting. Also, check the resistance of all motor wires to make sure there isn't an open connection. Lastly, a locked rotor could be the problem; pull the pump and check for any debris.
  • E
    edwardwhitneyAug 27, 2025
    Why is the Warning LED flashing on my Pentair Controller?
    • S
      Sean PetersonAug 27, 2025
      If the Warning LED is flashing on your Pentair Controller, verify the ground wire is connected on both the incoming voltage side and the motor side of the Drive. This issue can arise from an ungrounded Drive, especially when the ground detection parameter is disabled. With the power disconnected, use an ohmmeter to verify which pipe the Drive’s transducer is connected to, and also verify that the input ground wire is at the same potential. Verify the input ground is connected all the way back to the electrical panel.
  • R
    Rebecca LarsonAug 28, 2025
    What causes a Ground Fault on a Pentair Controller?
    • N
      Nicole MorganAug 28, 2025
      If your Pentair Controller indicates a 'Ground Fault', inspect the ground wire for a short to the motor phase wire, or check the insulation integrity with a megger. Also, be aware that a motor cable length exceeding 1000 ft is not recommended, as it can cause a ground fault.
  • T
    Thomas KingAug 30, 2025
    How do I troubleshoot a Dry Run error on my Pentair intellidrive pid10?
    • D
      David JohnsonAug 30, 2025
      If your Pentair Controller is showing a 'Dry Run' error, it might be due to operation at open discharge. You may need to reduce Dry Run Sensitivity pressure or apply back pressure on the transducer. Check for a pipe break or large leak. Also, check the water level in the well. Finally, the drive may not be reading the transducer signal. Check the linearity of the transducer, as it may be damaged.
  • J
    Jessica HicksSep 1, 2025
    What causes Over Temperature on Pentair Controller?
    • B
      Benjamin BoltonSep 1, 2025
      If your Pentair Controller displays 'Over Temperature', ensure the ambient temperature is not above 50°C (122°F). Check for an inoperable or obstructed fan. Also, ensure that the vents are not obstructed.
  • V
    Veronica MaddenSep 2, 2025
    What does 'System Not Grounded' mean on my Pentair Controller?
    • J
      Jeremy FinleySep 2, 2025
      If your Pentair Controller is displaying a 'System Not Grounded' error, the Ground Detect parameter can be disabled, but will reactivate after 72 hours. It also can be caused by unbalanced or three phase incoming voltage. Line to line voltage must be twice line to ground voltage.
  • A
    Alicia MathewsSep 4, 2025
    How to troubleshoot Open Transducer error on Pentair intellidrive pid10?
    • S
      Scott PerezSep 4, 2025
      If your Pentair Controller shows an 'Open Transducer' error, check that all transducer wires are securely connected and inspect for damaged cable insulation. Verify the proper wiring of all transducer wires and ensure the cable connector is securely attached to the transducer. Check the electrical system for ground loops or no ground connection. Also, make sure the transducer wires are correctly placed, with red in AI+ and black in AI-. Finally, the transducer may have failed.
  • B
    Brent ColeSep 6, 2025
    What to do for Low Amps on Pentair intellidrive pid10?
    • E
      evelyn03Sep 6, 2025
      If your Pentair Controller is showing 'Low Amps', try increasing the Minimum Speed to 35 Hz. Wait 20 minutes, then restart the pump. Check all motor connections at the Drive. The issue might be due to a missing motor phase or an undersized pump.

Summary

Safety

Important Safety Instructions

Core safety guidelines for installation, operation, and maintenance of the PENTEK INTELLIDRIVE VFD.

Description

Specifications;Ratings

Details the input voltage, frequency, ambient temperature, output connections, and enclosure type.

Installation

Circuit Breaker and Wire Sizes

Provides a table for selecting appropriate circuit breakers and wire sizes based on motor type and HP.

Wiring

Instructions for connecting input power and motor wires to the Drive terminals.

Pump Connections

Guidance on connecting output wires to submersible and above-ground pump motors.

Initial Startup

Initial Startup and Programming Procedures

Outlines the initial setup process for the PENTEK INTELLIDRIVE, including programming.

Service Factor Amps

Explains the importance of entering the correct Service Factor Amps for motor performance.

Troubleshooting

Troubleshooting Faults

Lists common faults, their possible causes, and solutions for diagnosis and repair.

Troubleshooting Continued

Continues the list of faults, causes, and solutions, including issues like Open Transducer and Over Temperature.

Software Updates

Updating Software on the Drive

Step-by-step guide on how to install new software onto the PENTEK INTELLIDRIVE.

Pentair intellidrive pid10 Specifications

General IconGeneral
BrandPentair
Modelintellidrive pid10
CategoryController
LanguageEnglish