Security Context
3 Security Context
From the security point-of-view, the responsible plant operator requires to take the following
measures:
• Limit the access for the workstations with an installation of VisuNet CC.
• Limit the access of the file store which contains the project files and stored data.
• The workstation with an installation of VisuNet CC should be connected to an network
which is managed by the IT.
• Ensure only the following Ports are open.
• For the Intranet which contains the RM Shell devices:
- VisuNet CC Discovery Port outgoing UDP 3702 and 137
- VisuNet CC Download/Upload Port outgoing TCP 8023
- VisuNet CC Session Shadowing Port outgoing TCP 5900
- VisuNet CC Default Secure Tunnel Port outgoing TCP 22314
- Factory Reset communication Port outgoing TCP 23314
• For the Internet:
- Update Service outgoing Port 443 TCP to the domain www.pepperl-fuchs.com