68 5756B
Controller Board Messages (examples) (* see IBS SYS DIAG DSC UM E Diagnostic Guide)
Message Parameter Extended
parameter
Description/Remedy
USER 09DE code*
Parameterization memory was activated but is not inserted.
RBUS X.Y code*
A remote bus error occurred in bus segment X.
LBUS X.Y code*
A local bus error occurred in bus segment X.
OUT2 X.Y code*
A remote or local bus error occurred in bus segment X.
OUT1 X.Y code*
A remote bus error has occurred after device X.Y.
Insert the IBS MC FLASH parameterization memory in the controller board.
Check device X.Y, its power supply and the remote bus cable leading to the device.
Check the local bus device X.Y and the local bus cabling leading to the device.
Check the local bus branching off from device X.Y.
Check the remote bus connection branching off from device X.Y, the power supply of
the following device or the device itself.