The zone is automatically bypassed after triggering the alarm three
consecutive times. It will be reinstated when the system/partition is
disarmed, or the
Auto-bypass Limit
time elapses; see 8, on page 24.
A different tone will be sounded when the zone triggers the alarm
The zone will re-trigger the alarm as long as it is open.
This attribute can only be used, if the Trigger
Sirens attribute is also selected.
The keypad’s buzzer will sound beeps throughout the alarm time
Users can temporarily bypass the zone
4.3 Copy Zones
System Configuration
Zones
Copy Zones
Select between copying a single zone’s attributes, type, partitions, and name to other zones,
and copying succeeding zones to a different location.
1) Single to Multiple
2) Multiple to Multiple
4.3.1 Single to Multiple
1) Copy Zone to Zones: select the zone to be copied and to which zone/s.
2) Copy Options:
The parameters from the zone attribute screen
The partitions that the zone is allocated to
4.3.2 Multiple to Multiple
1) Define a group of consecutive zones to be copied.
2) Select a zone from which the zones will be copied to; for example, if you select to copy
zones 21-34 (14 zones) and select zone 47, the 14 zones will be copied to zones 47-60.
3) Copy Options: see above.
4.4 Partitions Names
System Configuration
Zones
Partitions Names
Partitions can have unique names that will appear in the contacts reports and the event memory.
Use # or * to scroll and select the partition.
▪ Name: user text, up to 16 characters.