ATR401 - User manual 39
32 Derivative Time
Normally ¼ of integral time.
0.0…999.9 seconds. 0 derivative disabled, Default: 0.0.
33 Cycle Time
Cycle time (for P.I.D. on remote control switch 10 / 15 sec., for P.I.D. on SSR
1 sec.) or servo time (value declared by servo-motor manufacturer).
0.1…300.0 seconds, Default: 10.0.
34 Lower Limit Output Percentage
Select minimum value for command output percentage.
0…100%, Default: 0%.
Example: with selected as 0...10 V and set at 10%, command
output can change from a min. of 1 V to a max. of 10 V.
35 Upper Limit Output Percentage
Selects maximum value for command output percentage.
0…100%, Default: 100%.
Example: selected as 0...10 V and selected as 90%,
command output may vary between 0V and max. 9 V
36 Degree
Select degree type.
Centigrade (Default)
Fahrenheit
37 Alarm 1
Alarm 1 selection. Alarm intervention is correlated to AL1.
Disabled (Default)
Absolute alarm, referring to process
Band alarm
Upper deviation alarm
Lower deviation alarm
Absolute alarm, referring to command setpoint
Status alarm (active in Run / Start)
Cooling action
Load control alarm (Heater Break Alarm)
Sensor failure alarm (Loop Break Alarm)
Example: status of contactor/ SSR or heating elements