46 ATR401 - User manual
70 Alarm 4 Led
De nes led A4 status corresponding to relevant contact
ON with open contact
ON with closed contact (Default)
71 Alarm 4 Delay
-600…+600 seconds.
Negative: delay at exit from alarm. Positive: delay at starting of alarm.
Default: 0.
72 Alarm 4 Setpoint Protection
Alarm 4 set protection. Does not allow the user to change set value
Modi cation allowed (Default)
Protected
Protected and not visualized
73 Current Transformer
Activation and range for current transformer
0 Disabled (Default)
1…200 Ampere
74 Heater Break Alarm Threshold
Heater Break Alarm activation threshold
0.0 Disabled alarm
0.1...200.0 Ampere
Default: 50.0
75 Heater Break Alarm Delay
Heater Break Alarm activation delay
00.00…60.00 mm.ss
Default: 01.00
76 Cooling Fluid
Type of refrigerant uid for heating / cooling P.I.D.
Air (Default)
Oil
Water