46 ATR401 - User manual
70  Alarm 4 Led
De nes led A4 status corresponding to relevant contact
 ON with open contact
  ON with closed contact (Default)
71  Alarm 4 Delay
-600+600 seconds.
Negative: delay at exit from alarm. Positive: delay at starting of alarm.
Default: 0.
72  Alarm 4 Setpoint Protection
Alarm 4 set protection. Does not allow the user to change set value
 Modi cation allowed (Default)
 Protected
 Protected and not visualized
73  Current Transformer
Activation and range for current transformer
0 Disabled (Default)
1…200 Ampere
74  Heater Break Alarm Threshold
Heater Break Alarm activation threshold
0.0 Disabled alarm
0.1...200.0 Ampere
Default: 50.0
75  Heater Break Alarm Delay
Heater Break Alarm activation delay
00.00…60.00 mm.ss
Default: 01.00
76  Cooling Fluid
Type of refrigerant  uid for heating / cooling P.I.D.
 Air (Default)
 Oil
 Water