Pixsys ATR620 - ATR620 Alarm Operating Modes; Band Alarm (Setpoint-Process); Deviation Alarm (Setpoint-Process); General Alarm (Process)

Pixsys ATR620
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
86
30 Alarms operating
Three alarms can be programmed and be connected to outputs
OUT, A1, A2 ( if they are not used for control). The following
graphs describe the programmable operatings.
Band alarm (setpoint-process)
Comparison value
Hysteresis
Hysteresis
Time
OUT/A1/A2
P-14/P-16
Alarm can be :
active outside band
active inside band
Example: outside
Deviation alarm (setpoint-process)
Time
Comparison value
Hysteresis
OUT/A1/A2
P-14/P-16
Alarm can be :
active above comparison value
active below comparison value
Example: upper deviation
General alarm (process)
Comparison value
Hysteresis
Time
P-14/P-16
OUT/A1/A2
Alarm can be :
active over process value
active below process value
Example: above process value