56
22.3 Software data
Control algorithm
ON-OFF with hysteresis,
P, PI, PID, PD time proportioning
Proportional band
0...9999°C or °F
Integral time
0...9999 sec (0 excludes)
Derivative time
0,0...999,9 sec (0 excludes)
Software functions
Auto-Tuning , configurable alarms
cycles
15 cycles, max 20 segments (steps) for
each cycle + function “simple controller”
with programmable setpoint
Remote control
Setpoint received by analog or serial input
Manual function
Increase/decrease manually the percentage
of output (manual control of power)
23 Sizes and installation