User’s Manual of IMG-110T
-51-
Inter-character
Timeout
(0ms,10-500ms)
In a single frame, the time difference is between a single character and the next
character. When the value is 0, the default is 3.5T time, which is equal to 3.5 characters.
The available range is 10-500ms.
Inter-frame Delay
(0ms,10-500ms)
The current RTU response with the next RTU request is between the time intervals. The
default is 0ms. This feature is to avoid the RTU request from the station equipment. Set
the time interval to facilitate the RTU from the station equipment that has adequate time
to handle the request. The available range is 10-500ms.
Button
: Click to apply changes.