2.4.1.7 IN-TANK LEAK TEST DETAILED RESULTS
Log
Inventory Inventory
deLivery Deliveries
SALES Bulk Sales
tHEFtS Thefts
Orders Product Reordering Report
Water Bottom Water Removal
tank Leak In-Tank Leak Test Detailed Results
Leak Hist In-Tank Leak Test History
LIne Leak LS300 Line Leak Test
ALArMS Alarms
Events Events
return Return
tank Leak In-Tank Leak Test: detailed In-Tank Leak Test results showing the average change at the end of each
hour. The settings for In-Tank Leak Testing are found both in the Tank Leak submenu of the
Configuration menu and in the Leak Test menu.
Record Storage Capacity: 12, 1 per Tank Channel
TMS Configuration Prerequisites:
Leak Test menu: Scheduling, duration, and other test controls.
Configuration menu, Tank Leak submenu: Test configuration including Test Type and Leak Rate.
Group ID: Tank Channel Number.
Record Identification Data:
mm-dd Date (Month-Day): Date the In-Tank Leak Test completed.
Note: an empty record will show 00-00.
Starttime Start Time: Time the In-Tank Leak Test began.
Note: time stored in 24 hr. format
Examples 12’00 = 12 Noon 23’59 = 11:59 PM 00’00 = Midnight
End time End Time: Time the In-Tank Leak Test completed.
Note: time stored in 24 hr. format
tank Name Tank Name: As Assigned in the Configuration menu, Tank submenu.
Prod type Product Type: As Assigned in the Configuration menu, Tank submenu.
tank id Tank ID Number: As Assigned in the Configuration menu, Tank submenu.
Captured Data:
Net Begin Beginning Net Volume: Total Net Volume at the Beginning of the In-Tank Leak Test.
Net End Ending Net Volume: Total Net Volume at the End of the In-Tank Leak Test.
Beg temp Beginning Temperature: Average Product Temperature at the Start of the In-Tank Leak Test.
End temp Ending Temperature: Average Product Temperature at the End of the In-Tank Leak Test.
LeakLimit Leak Limit: Leak Threshold for determining Pass/Fail. See Configuration menu, Tank Leak
submenu, Leak Limit setting.
Rate GPH Leak Rate GPH/LPH: Observed average hourly gain/loss of Gross Volume.
ResULt Test Result: PASS or FAIL. In-Tank Leak Test result.
Rate hr1 Leak Rate Hour-1: Observed average gain/loss of Gross Volume at the end of the first hour.
Rate hr2-8 Leak Rate Hour-2-8: same as above averaging in each additional hour 2-8 inclusive.
Exit Tank Leak submenu:
Return Return: Press EDIT (TEST) to exit Tank Leak submenu.
Note: Press STEP (MODE) to return to top of Tank Leak submenu showing mm-dd
(Month-Day)