OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 66
2.4.3.16 SYSTEM CONFIGURATION TANK LEAK
Config
Header Header General System Settings
tank Tank Tank Channel specific including geometry and SetPoints
Probe Probe Level Gauging Probe settings
ReLy tank Relay Tank Relay Assignments to Tank Channel Specific conditions
ReLy cc Relay CC Relay Assignments to individual Non-Hazardous CC Inputs
ReLy Sens Relay Sensor Relay Assignments to individual Leak/Point Level Sensor Inputs
ReLy LLP Relay LLP Relay Assignments to external LS300 Line Leak failures
ReLy Site Relay Site Relay Assignments to Site-Specific conditions
ReLy Mode Relay Mode Relay-specific behavior settings
cc input Non-Hazardous Contact Closure (CC) Inputs
Sensr inp Leak/Point Level Sensor Inputs
Inventory Shift Inventory Report Schedule
tHeft Theft Detection (Hours of operation)
Modem Modem/Serial C Communications
diaL out Auto-Dial out - Setup for selected Alarms or Tank information
tank LEAk In-Tank Leak Test Setup
AnaLogout Analog Outputs
tAnk LEAk In-Tank Leak Test Setup: The configuration of the In-Tank Leak Test is defined in this submenu
in conjunction with scheduling/time related settings in the Leak Test menu. The Group ID references
the Tank Channel being configured.
Prerequisites for running a valid In-Tank Leak Test are as follows (Refer to the National Workgroup website,
www.nwglde.org, or contact Pneumercator for up-to-date information):
Tank requirements
o Single-Wall Underground Storage Tank
o Isolated (Not Manifolded)
o Not Heated or Pressurized
o Up to 75,000 Gallon [283,900 Liter] capacity
0.2 GPH [0.8 LPH] in 2 hours for tanks up to 20,000 Gallons [75,700 Liters]
0.1 GPH [0.8 LPH] in 8 hours for tanks up to 20,000 Gallons [75,700 Liters]
0.2 GPH [0.8 LPH] in 8 hours for tanks up to 75,000 Gallons [283,900 Liters]
Qualifying Petroleum Product as defined by the Federal EPA.
MP450S
o Riser Mounted
o 4-inch Urethane or Buna-N floats
o 5 Temperature Sensors
After enabling a test, the following front panel display characteristics may appear while in View Mode.
When the Mode button is pressed and released, the TMS will normally display the Tank Name. In
addition, if an In-Tank Leak Test is scheduled, a short letter L (/) will appear on the far-left directly above
Tank ID number.
The TMS will show a blinking short letter L (/) to the right of the Tank ID number if the In-Tank Leak Test
is Paused.
When an In-Tank Leak Test is actively running, a short letter L (/) will appear to the right of the Tank ID
number.
test En In-Tank Leak Test Enable: Enable the In-Tank Leak Test for the specified Tank Channel.
Entry Type: select list
Range Limits: No, Yes
Default/Initialized value: no