OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 27
2.4.1.11 EVENTS LOG
Log
Inventory Inventory
deLivery Deliveries
SALES Bulk Sales
tHEFtS Thefts
Orders Product Reordering Report
Water Bottom Water Removal
tank Leak In-Tank Leak Test Detailed Results
Leak Hist In-Tank Leak Test History
LIne Leak LS300 Line Leak Test
ALArMS Alarms
Events Events
return Return
Events Events: Contains System Errors that represent a possible hardware problem with the system including
probes, sensors, and field cabling. Select Non-Alarm Warnings are also recorded in this Log. See list on
following page for a basic list of Events or Appendix A for a detailed list.
Record Storage Capacity: 8
TMS Configuration Prerequisites: N/A
Group ID: Record Number.
Record Identification Data:
mm-dd Date (Month-Day): Date the Error/Warning occurred.
Note: an empty record will show 00-00.
HH'mm Time (Hour’ Minute): Time the Error/Warning occurred.
Note: time stored in 24 hr. format
Examples: 12’00 = 12 Noon 23’59 = 11:59 PM 00’00 = Midnight
Captured Data:
Error Num Error Number: A 2-digit numeric Error Number.
Warn Num Warning Number: A 2-digit numeric Warning Number.
tank id Tank ID: As Assigned in the Configuration menu, Tank submenu.
Input id Input ID: As Assigned in the Configuration menu, CC Input or Sensor Input submenu
Event id Event ID: Category of the Event including Probe, Sensor, or Power.
DetaiL Detail: Provides additional details for the reported Error or Warning
Exit Events submenu:
Return Return: Press EDIT (TEST) to exit Events submenu.
Note: Press STEP (MODE) to return to top of Events submenu showing mm-dd (Month-Day)