2.4.3.14 SYSTEM CONFIGURATION – MODEM
Config
Header Header – General System Settings
tank Tank – Tank Channel specific including geometry and SetPoints
Probe Probe – Level Gauging Probe settings
ReLy tank Relay Tank – Relay Assignments to Tank Channel Specific conditions
ReLy cc Relay CC – Relay Assignments to individual Non-Hazardous CC Inputs
ReLy Sens Relay Sensor – Relay Assignments to individual Leak/Point Level Sensor Inputs
ReLy LLP Relay LLP – Relay Assignments to external LS300 Line Leak failures
ReLy Site Relay Site – Relay Assignments to Site-Specific conditions
ReLy Mode Relay Mode – Relay-specific behavior settings
cc input Non-Hazardous Contact Closure (CC) Inputs
Sensr inp Leak/Point Level Sensor Inputs
Inventory Shift Inventory Report Schedule
tHeft Theft – Detection (Hours of operation)
Modem Modem/Serial C Communications
diaL out Auto-Dial out - Setup for selected Alarms or Tank information
tank LEAk In-Tank Leak Test – Setup
AnaLogout Analog Outputs
Modem Modem/Serial C Communications: Enables and configures the optional modem types (P/N
900433-x or 900503-1) or optional Serial C (P/N 900571-x) Interfaces.
Modem Modem/Serial C Interface Option Enable: Select the interface currently installed in the TMS.
Entry Type: select list
Range Limits: nonE (None): No Communications option installed
IntErnAL (Internal): 900433-x Modem installed
FCS Mdm (Facsimile Modem): 900503-1 Faxmodem installed
Port Mdm (Port Modem): Third-Party RS-232 modem connected to Serial A
SErIAL C (Serial C): 900571-x Serial option installed
CELL Mdm (Cell Modem): PCO Cell Modem installed (Future Use)
RS485 Md (RS-485 Mode): 900571-3 or 900571-4 installed AND using RS-485
Default/Initialized value: nonE
FCS LOCAL Fax Sender ID Phone Number: Up to 14 digits used to identify the origin of the fax transmission
FCS Area on the leading edge of the fax as currently required by federal regulations. Complete 14-digit
value formed as FCS Area + FCS Local, each with a 7-digit maximum.
Entry Type: 7-digit numeric each
Range Limits: 0-9, _ (Blank)
Default/Initialized value: _______
Note: The Current Federal Communications Commission regulation part 68, Section 68.318 (c) (3) states that it is
illegal to transmit a fax in the United States which does not contain the following sender information:"...in a margin on
the top or bottom of each transmitted page or on the first page of the transmission, the date and time it was sent and
an identification of the business, other entity, or individual sending the message and the telephone number of the
sending machine of such business, other entity or individual."
Baud rate Baud Rate: For modems, this defines the Maximum Baud Rate allowed by the modem when
negotiating connection speed. For 900571-x, defines the baud rate for Serial C.
Entry Type: Select list
Range Limits: 2400, 1200, 4800, 9600, 14400
Default/Initialized value: 2400
diaL TYPE Dial Type: Select TOUCH (Touch-Tone) for phone lines that support pushbutton phones or
PULSE for phone lines that only support rotary dial phones
Entry Type: Select list
Range Limits: Tone, Pulse
Default/Initialized value: tone