OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 59
2.4.3.12 SYSTEM CONFIGURATION – INVENTORY
Config
Header Header – General System Settings
tank Tank – Tank Channel specific including geometry and SetPoints
Probe Probe – Level Gauging Probe settings
ReLy tank Relay Tank – Relay Assignments to Tank Channel Specific conditions
ReLy cc Relay CC – Relay Assignments to individual Non-Hazardous CC Inputs
ReLy Sens Relay Sensor – Relay Assignments to individual Leak/Point Level Sensor Inputs
ReLy LLP Relay LLP – Relay Assignments to external LS300 Line Leak failures
ReLy Site Relay Site – Relay Assignments to Site-Specific conditions
ReLy Mode Relay Mode – Relay-specific behavior settings
cc input Non-Hazardous Contact Closure (CC) Inputs
Sensr inp Leak/Point Level Sensor Inputs
Inventory Shift Inventory Report Schedule
tHeft Theft – Detection (Hours of operation)
Modem Modem/Serial C Communications
diaL out Auto-Dial out - Setup for selected Alarms or Tank information
tank LEAk In-Tank Leak Test – Setup
AnaLogout Analog Outputs
Inventory Shift Inventory Report Schedule: Schedules up to three Inventory Snapshots per day for each of the
seven days of the week. The Snapshots are recorded in the Inventory Log and are optionally printed
on the TMS printer. The 36-record capacity of the Inventory Log allows for one day of Snapshots for
the 12-tank maximum supported by the TMS3000.
Hour 1 Hour 1: The TMS will record an Inventory Snaphot for every unique time configured in HOUR
1, HOUR 2, and HOUR 3 for the enabled Days of the Week. For example, if the TMS had HOUR
1 and HOUR 2 set for 00’00 (Midnight) and HOUR 3 set for 12’00 (Noon), the TMS would record
TWO Inventory Snapshots for each enabled Day of the Week, one at midnight and one at noon.
Entry Type: 4 digit numeric hours, minutes
Range Limits: 00’00 – 23’59. (24-hour clock format)
Default/Initialized value: 00’00
Example 12’00 = 12 Noon 23’59 = 11:59 PM 00’00 = Midnight
Hour1 Prt Hour 1 Print: TMS will print the Inventory Snapshot from the TMS printer at the time defined in
Hour 1, when enabled.
Entry Type: Select
Range Limits: No, Yes
Default/Initialized value: no
Hour 2 Hour 2: The TMS will record an Inventory Snaphot for every unique time configured in HOUR
1, HOUR 2, and HOUR 3 for the enabled Days of the Week. See Hour 1 example.
Entry Type: 4 digit numeric hours, minutes
Range Limits: 00’00 – 23’59. (24-hour clock format)
Default/Initialized value: 00’00
Example 12’00 = 12 Noon 23’59 = 11:59 PM 00’00 = Midnight
Hour2 Prt Hour 2 Print: TMS will print the Inventory Snapshot from the TMS printer at the time defined in
Hour 2, when enabled.
Entry Type: Select
Range Limits: No, Yes
Default/Initialized value: no