OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 48
2.4.3.4 SYSTEM CONFIGURATION RELAY TANK
Config
Header Header General System Settings
tank Tank Tank Channel specific including geometry and SetPoints
Probe Probe Level Gauging Probe settings
ReLy tank Relay Tank Relay Assignments to Tank Channel Specific conditions
ReLy cc Relay CC Relay Assignments to individual Non-Hazardous CC Inputs
ReLy Sens Relay Sensor Relay Assignments to individual Leak/Point Level Sensor Inputs
ReLy LLP Relay LLP Relay Assignments to external LS300 Line Leak failures
ReLy Site Relay Site Relay Assignments to Site-Specific conditions
ReLy Mode Relay Mode Relay-specific behavior settings
cc input Non-Hazardous Contact Closure (CC) Inputs
Sensr inp Leak/Point Level Sensor Inputs
Inventory Shift Inventory Report Schedule
tHeft Theft Detection (Hours of operation)
Modem Modem/Serial C Communications
diaL out Auto-Dial out - Setup for selected Alarms or Tank information
tank LEAk In-Tank Leak Test Setup
AnaLogout Analog Outputs
ReLy tAnk Relay Tank Triggers: Each tank alarm condition can affect up to three relay outputs. These are
generally used to support select remote alarms or provide signal outputs for third party systems.
The TMS3000 currently supports up to 32 Relay Outputs and the TMS2000 systems currently
support up to 18 Relay Outputs. The Group ID shown corresponds to the hardware Tank Channel
and NOT the Tank ID.
LEAk trig Leak Trigger: A failed In-Tank Leak Test.
Entry Type: numeric list
Range Limits: Each Relay: No (No Relay Assignment), 1-32 (TMS3000), 1-18 (TMS2000)
Note: Each assignment separated by decimal point.
Default/Initialized value: no.no.no
SP1 trig Product SetPoint Triggers: (3 Product SetPoint Firmware Only: Vxx99xx or Vxx00xx).
SP2 trig Product SetPoints. Generally represent High and/or Low Product.
SP3 trig Entry Type: numeric list
Range Limits: Each Relay: No (No Relay Assignment), 1-32 (TMS3000), 1-18 (TMS2000)
Note: Each assignment separated by decimal point.
Default/Initialized value: no.no.no
CrtH trig Product SetPoint Triggers: (6 Product SetPoint Firmware Only: Vxx01xx).
HiHi trig Product SetPoints. Generally represent High and/or Low Product.
High trig Entry Type: numeric list
Lo trig Range Limits: Each Relay: No (No Relay Assignment), 1-32 (TMS3000), 1-18 (TMS2000)
LoLo trig Note: Each assignment separated by decimal point.
CrtL trig Default/Initialized value: no.no.no
h2o trig Water SetPoint Trigger: Bottom Water SetPoint Alarm
Entry Type: numeric list
Range Limits: Each Relay: No (No Relay Assignment), 1-32 (TMS3000), 1-18 (TMS2000)
Note: Each assignment separated by decimal point.
Default/Initialized value: no.no.no
return Return: Press EDIT (TEST) to exit Relay Tank submenu.
Note: Press STEP (MODE) to return to top of Relay Tank submenu showing LEAk trig
(Leak Trigger)