OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 74
APPENDIX A – TMS CONSOLE AL
ARM
& EVENT
COND
ITIONS TABLES
Alarm Conditions:
The following alarm
condi
tions
are recorded
in the
Alarm Log
and
are printed
automatically
if printer
is enabled.
Alarm conditions
are also
user
programmable
to auto-dial
out upon
alarm
.
Leak
and
Setpoin
t alarms
will produce
both audible
and visual
LED annunciators
until ackn
owledged
via Front
panel
or Edit enable
butto
ns. Visua
l LED
conditions
will continue until
the specific le
ak or setpoint
co
nditions are
corrected.
Theft alarms will produce
an audible
annunciator
and appear
on the TMS
display showing
a theft
message
condition
across
the display.
Theft alarms can
only be ackn
owledged via t
he Edit enabl
e button. The displayed mes
sage will conti
nue until the c
onditio
n is cor
rected.
CC and
ISCC
alarms
will produce
an audible
annunciator
and appear
on the TMS
display showing a CC or ISCC
alarm
message
across
the display.
The
audible
annu
nciator
can be ackn
owledge
d via Front
panel
or Edit
enable buttons.
The
CC or ISCC
displayed
message
will continue
until the condi
tion is
correc
ted.
larm Des
cription
Display and
Printout Onl
y
Displa
y, Printout, and Co
mpute
r Format
Status
Detail
Description
Item ID
Nam
e
Notes
Leak
n/a
IN-TANK
LEAK A
LARM
tank #
n/a
Failure of an In-Tank Le
ak Test
SP1
n/a
PRO
DUCT SETPOINT #1
ALARM
tank #
SP1
Nam
e
Meets or exceeds the programmed
produc
t SetPoint.
Factory
default
value
is for a HIGH HIGH
alarm
at or
above 95% of
Gross Volum
e.
SP2
n/a
PRODUCT SETPOIN
T #2 ALARM
tank #
SP2
Nam
e
Meets or exceeds the programmed
produc
t SetPoint.
Factory
default
value
is for a HIGH
alarm
at or abov
e
90% of Gross
Volume
.
SP3
n/a
PRO
DUCT SETPOINT #3
ALARM
tank #
SP3
Nam
e
Meets or exceeds the programmed
produc
t SetPoint.
Factory
default
value
is for a LOW
alarm
at or below
20% of Gross
Volume
.
Water
n/a
WATER SE
TPOINT A
LARM
tank #
n/a
Meets or exceeds the programmed
water SetPoint.
Factory
default
value
is 2 inches
[51 millimeters]
or
higher of bottom
water in ta
nk.
Theft
n/a
THEFT ALARM
tank #
n/a
Theft of produc
t from the tank
CC
Open
CONTACT
CLOSU
RE ALARM -
OPE
N
cc #
Contact Clos
ure
Name
Device
wired to CC Input is in alarm
CC
Close
d
CONTACT
CLOSU
RE ALARM -
CLOSE
D
cc #
Contact Clos
ure
Name
Senso
r
Open
POINT SENSOR A
LARM -
OPEN
sensor #
Sensor Nam
e
Point level
(High, L
ow, etc.) sensor is in alarm
Senso
r
Close
d
POINT SENSOR A
LARM -
CLOSED
sensor #
Sensor Nam
e
Senso
r
Open
LEAK SENS
OR ALARM -
OPEN
sensor #
Sensor Nam
e
Non-discrimi
nating leak se
nsor is in alarm
Senso
r
Close
d
LEAK SENS
OR ALARM - CLOSED
sensor #
Sensor Nam
e
Senso
r
Produc
t LEAK SENSOR ALARM -
PROD
UCT sensor #
Sensor Nam
e
Discriminatin
g leak sensor i
s in alarm
Senso
r
Water
LEAK SENSOR ALARM -
WATER
sensor #
Sensor Nam
e
Note: IS
CC or Intrinsically
Safe Contact C
losure is syno
nymous
with Leak/Pt. Level
Sensor