OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 50
2.4.3.6 SYSTEM CONFIGURATION RELAY SENSOR
Config
Header Header General System Settings
tank Tank Tank Channel specific including geometry and SetPoints
Probe Probe Level Gauging Probe settings
ReLy tank Relay Tank Relay Assignments to Tank Channel Specific conditions
ReLy cc Relay CC Relay Assignments to individual Non-Hazardous CC Inputs
ReLy Sens Relay Sensor Relay Assignments to individual Leak/Point Level Sensor Inputs
ReLy LLP Relay LLP Relay Assignments to external LS300 Line Leak failures
ReLy Site Relay Site Relay Assignments to Site-Specific conditions
ReLy Mode Relay Mode Relay-specific behavior settings
cc input Non-Hazardous Contact Closure (CC) Inputs
Sensr inp Leak/Point Level Sensor Inputs
Inventory Shift Inventory Report Schedule
tHeft Theft Detection (Hours of operation)
Modem Modem/Serial C Communications
diaL out Auto-Dial out - Setup for selected Alarms or Tank information
tank LEAk In-Tank Leak Test Setup
AnaLogout Analog Outputs
ReLy sens Relay Sensor (ISCC) Input Triggers: Each Leak/Point Level Sensor (ISCC) Input can affect up to
three relay outputs. The TMS3000 currently supports up to 32 Relay Outputs and the TMS2000
systems currently support up to 18 Relay Outputs. The Group ID shown corresponds to the
Leak/Point Level Sensor Input Number. Note: The Relay Sensor submenu was formerly identified
as the Relay ISCC (Intrinsically Safe Contact Closure) submenu.
sens trig Sensor (ISCC) Input Trigger: A Sensor Input can affect up to three relays.
Entry Type: numeric list
Range Limits: Each Relay: No (No Relay Assignment), 1-32 (TMS3000), 1-18 (TMS2000)
Note: Each assignment separated by decimal point.
Default/Initialized value: no.no.no
Return Return: Press EDIT (TEST) to exit Relay Sensor submenu.
Note: Press STEP (MODE) to return to top of Relay Sensor submenu showing sens trig
(Sensor Trigger)