OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 32
TEST LENGTH
START TIME
SCHEDULE TYPE
SCHEDULE RATE
4) Perform a
2 HOUR
test at
00:00
THIS
SUNDAY
4 HOUR
EVERY
MONDAY
8 HOUR
PERCENT VOLUME
TUESDAY
ON 1
ST
WEDNESDAY
ON 2
ND
THURSDAY
ON 3
RD
FRIDAY
ON 4
TH
SATURDAY
DAY
MONTH
MINUTE
Perform a 4-hour test at 12:00AM midnight every day when the percent volume is at least the value in threshold.
TEST LENGTH
START TIME
SCHEDULE TYPE
SCHEDULE RATE
5) Perform a
2 HOUR
test at
09:30
THIS
SUNDAY
4 HOUR
EVERY
MONDAY
8 HOUR
PERCENT VOLUME
TUESDAY
ON 1
ST
WEDNESDAY
ON 2
ND
THURSDAY
ON 3
RD
FRIDAY
ON 4
TH
SATURDAY
DAY
MONTH
MINUTE
Perform an 8-hour test at 9:30am on the third Saturday of every month.
Once all of the settings have been reviewed in Configuration/Tank Leak as well as the above In-Tank Leak Test
scheduling, the TMS can be configured to start the test.
CONTROL
START In Manual mode, this starts the test. In Timed and Timed-Relay mode, this starts the scheduler
for the TMS to run the In-Tank Leak Test based on the defined schedule.
STOP In Manual, Timed, and Timed-Relay modes, the test will never run with this set.
PAUSE This is an unused feature at this time
RUN This is not a setting but is a status that represents an In-Tank Leak Test is currently running on
the selected tank.