OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 45
2.4.3.3 SYSTEM CONFIGURATION PROBE
Config
Header Header General System Settings
tank Tank Tank Channel specific including geometry and SetPoints
Probe Probe Level Gauging Probe settings
ReLy tank Relay Tank Relay Assignments to Tank Channel Specific conditions
ReLy cc Relay CC Relay Assignments to individual Non-Hazardous CC Inputs
ReLy Sens Relay Sensor Relay Assignments to individual Leak/Point Level Sensor Inputs
ReLy LLP Relay LLP Relay Assignments to external LS300 Line Leak failures
ReLy Site Relay Site Relay Assignments to Site-Specific conditions
ReLy Mode Relay Mode Relay-specific behavior settings
cc input Non-Hazardous Contact Closure (CC) Inputs
Sensr inp Leak/Point Level Sensor Inputs
Inventory Shift Inventory Report Schedule
tHeft Theft Detection (Hours of operation)
Modem Modem/Serial C Communications
diaL out Auto-Dial out - Setup for selected Alarms or Tank information
tank LEAk In-Tank Leak Test Setup
AnaLogout Analog Outputs
Probe Probe: Provides probe-specific settings that, when combined with the configuration in the Tanks
submenu, allow the TMS to provide the highest degree of accuracy available. The Group ID shown
corresponds to the hardware Tank Channel and NOT the Tank ID.
Probe CF Probe Calibration Factor: Required for providing accurate tracking of the float movement on the
probe stem of all MP4xx probes. Found at the top of the probe on a label around the probe head
(MP45x) or secured to the probe cable (MP46x).
Entry Type: 4-digit numeric
Range Limits: 8.000 9.999
Default/Initialized value: 9.000
Probe typ Probe Type: The model number of the level gauging probe must be entered for accurate results.
An incorrect selection may result in Probe Errors or inaccurate information. Found at the top of
the probe on a label around the probe head (MP45x) or secured to the probe cable (MP46x).
Entry Type: select list
Range Limits: See below table
Default/Initialized value: MP450
MP450
MP450
MP440
MP440
MP452
MP452
MP460
MP460
MP451
MP451
MP461
MP461
MP462
MP462
MP463
MP463
2-412
2-412
2-501
2-501
UP420
UP420
UP420 Note: See Appendix D for calibration instructions
2-412/2-501 Note: See Appendix E for calibration instructions
Probe Len Probe Length: Determines the location of the temperature sensors within the probe stem of the
MP4xx and the gauging length of the 2-412, 2-501, and sensing length of the UP420.
Entry Type: 5-digit numeric
Range Limits: Up to 1999.9 inches [Up to 49,999 millimeters]
Default/Initialized value: 0.0 [0]
Prod HO Product Height Float Offset: Represents the adjustment to the raw probe level required to
compensate for both the float depth in the liquid and mounting height of the probe. Required to
provide accurate volume calculations and In-Tank Leak Test results. Calculated by taking the
difference between the raw probe level and a manual stick reading of the total liquid level.
Entry Type: 4-digit numeric
Range Limits: +/- 0.0 - 299.9 inches [+/- 0 7,999 millimeters]
Default/Initialized value: 0.0 [0]