OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 56
Inp Name Input Name: Name of CC Input specified to identify function of CC Input. The name USER
indicates a User-Defined CC Input Name. See next setting for User-Defined Name.
Entry Type: select list
Range Limits: See table below
Default/Initialized value: USEr
USEr
User-Defined
gEnrtr
Generator
RES 1
Reserve 1
RES 2
Reserve 2
RES 3
Reserve 3
RES 4
Reserve 4
L1PASS
Line 1 Pass
L1FAiL
Line 1 Fail
L2PASS
Line 2 Pass
L2FAiL
Line 2 Fail
L3PASS
Line 3 Pass
L3FAiL
Line 3 Fail
L4PASS
Line 4 Pass
L4FAiL
Line 4 Fail
Punp
Pump
User Name User-Defined Input Name: A 6-character alphanumeric name entered via TMSComm. Note that
this is a context sensitive setting that only appears if the CC Input Name is set for User
Entry Type: select list
Range Limits: 6-character alphanumeric. Must be entered via TMSComm.
Default/Initialized value: Input
NormaLLy Normal Contact State: The normal state of the signal wired to the CC Input. Commonly
connected devices include the RS2 (Test/Reset buttons) and CS-10 Current Sensor which are
both Normally Open.
Entry Type: select list
Range Limits: Open, Close
Default/Initialized value: CLOse
Logic En Logic Enable Group: Creates a Logic Group containing two or more CC Inputs defined by which
CC Inputs are assigned to a specific letter group. ALL inputs in the group must be active to
affect any Relay Outputs assigned to any of the CC Inputs in the group.
Entry Type: select list
Range Limits: Off, AND A AND H
Default/Initialized value: OFF
timedeLay Time Delay: A Time Delay applied to a condition going active or inactive may be applied to any
CC Input. For example. If a CC Inputs is used to monitor an external system, a Time Delay may
be applied to considering the CC Input in alarm to allow time for the external system to be
repowered without causing a false alarm.
Entry Type: select list
Range Limits: 00 SEC : Feature disabled.
)02 SEC : Delay reacting to condition activating for 2 seconds
)05 SEC : Delay reacting to condition activating for 5 seconds
)10 SEC : Delay reacting to condition activating for 10 seconds
)20 SEC : Delay reacting to condition activating for 20 seconds
(02 SEC : Delay reacting to condition deactivating for 2 seconds
(05 SEC : Delay reacting to condition deactivating for 5 seconds
(10 SEC : Delay reacting to condition deactivating for 10 seconds
(20 SEC : Delay reacting to condition deactivating for 20 seconds
Default/Initialized value: 00 SEC
Return Return: Press EDIT (TEST) to exit CC Input submenu.
Note: Press STEP (MODE) to return to top of CC Input submenu showing cc EnabLe
(CC Enable)