TMS4000 Operation Manual 2018-08-03.docx August 3, 2018
PAGE 22
2.3 HEADER
Site Name: Printed on system generated reports
Unit ID: Used to identify the TMS that generated a report. This is recorded in all Logs and is included
on all printouts from the TMS. This is also used, in part, to identify a TMS that is making a phone call
to a computer running Autopolling. See Unit ID.
Site ID: Used to identify the TMS that generated a report. This is recorded in all Logs and is included
on all printouts from the TMS. This is also used, in part, to identify a TMS that is making a phone call
to a computer running Autopolling. See Unit ID.
Horn Delay: Silences the integrated TMS horn after a delay set in minutes. Selecting None disables
this feature.
Leak Print Mode: Choice between printing all In-Tank Leak Test Results (Pass-Fail) or only Failing
results (Fail Only)
Ullage Limit: ullage is the free space in the tank. Factory default of 90% is used due to the fact that
most applications do not permit the filling of a tank above the 90% volume mark. Other options include
85%, 95%, and 100%.
Sales Enable: Enables Bulk Sales Tracking and records data in the Sales Log. Not used for
applications where simultaneous transactions can occur.
Line Leak Enable: Makes available the assignment of the Line Leak Channel number of the external
LS300 Line Leak console to a specific Tank Channel
File Export Prefix: The Prefix is prepended to the file name of the exported report saved to a USB
Flash Drive.