EasyManua.ls Logo

Pneumercator TMS4000 - Leak Test Scheduling - Scheduled

Pneumercator TMS4000
94 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OPERATION MANUAL TMS4000
TMS4000 Operation Manual 2018-08-03.docx August 3, 2018
PAGE 39
2.9.2 LEAK TEST SCHEDULING - SCHEDULED
A leak test may be scheduled to accommodate the needs of the sites and the requirements of the
regulatory agencies. Several examples are shown below.
Selecting a Test Frequency of ONCE provides the means of starting a single test at the time and date
configured above.
Selecting the radio button for On The nth Date Of The Month allows the user to run the test up to one
month in the future. If, for example, today’s date is September 15 and the value entered in the box is
14, the test will run on October 14th at the designated time. If the value entered is 15 but that time
has already past, then the test will run on October 15th at the designated time.
Selecting the radio button On Day of Week allows the test to be run up to one week ahead. The
example above show the setting as On Sunday which would cause the TMS to begin the test on
Sunday at the designated time.
If the test requires a minimum % Volume, be sure to check the box to establish that requirement. The
test will NOT run if the percent volume is below this threshold. The percentage value is configured in
the Setup/Config/Tanks/Leak Test menu (See Section 2.8).
Upon completion, the schedule will be satisfied and no further tests will be run until the TMS schedule
is reconfigured. This is generally used either to confirm a tank is not leaking on initial install or to
manually run a test after a failure to confirm the results.