OPERATION MANUAL TMS4000
TMS4000 Operation Manual 2018-08-03.docx August 3, 2018
PAGE 24
Enable: Activates the selected Tank Channel. The Tank Channel number is represented by the tabs
across the bottom. Use the small arrow buttons on the bottom right corner to access all available tank
channels or click on a visible tank tab number.
ID: Used to assign a custom 3 digit numeric tank ID to a tank channel. Default setting has the Tank
ID matching the Channel Number.
Tank Name: A name assigned to a tank to identify the stored product. Select from the list or type in a
16 character custom name.
Tank Tag: Printed on system generated reports
Product Type: Defines the coefficient of thermal expansion. Consult factory if product is not listed.
Product Code: Used to support V200 and V300 protocols. Not used in any calculations and is not
present on any reports.
Temperature: Selects whether or not the temperature reading is viewed. Shown as a constant zero
temperature if disabled. Temperature must be enabled for in-tank leak tests.
Water Float: Instructs the TMS to display the water level reported by the probe. This setting is
intended for use in applications where the water reading is not desired. The TMS displays a blank in
the water level field when disabled.
Theft Detect Enable: Enables a per tank setting for theft monitoring. See the Theft tab for more details.
Generator Tank: A special in-tank leak test mode intended for use on above ground generator tanks.
Identical to Auto Leak Test Mode without the monthly limitation.
Associate with Line Leak Channel: Used in the Line Leak Report to identify the tank that the tested
line supports. Only displayed if Line Leak Enable is checked in Header section.