OPERATION MANUAL TMS4000
TMS4000 Operation Manual 2018-08-03.docx August 3, 2018
PAGE 47
CC Enable: a CC Input can be enabled in one of several ways:
Relay: Used to control something whether it is a relay or an auto leak test. (RS2 Test button)
(CS-10)
Gate: Advanced functionality incorporates a logic AND gate into this input. It is paired with
other conditions that call out the same relay.
Alarm: Used to represent an alarm condition from an external device.
Acknowledge: Used to return a relay to its normal state (RS2 Reset button)
Line Pass: Specific to specific LS300 Line Leak console configurations. Used to filter out the
numerous passing tests and allow only one per month.
FP Horn Ack: Front Panel Horn Acknowledgement allows an external automation system to
send a dry contact signal to the TMS to silence the integrated TMS horn.
Trigger Group: Part of an advanced auto pump select feature where the pump paired with the
highest tank volume is selected. Consult factory for details.
Input Name: Select a name from the list or enter a 16 character custom name. Used to help to identify
the input.
CC Tag: Printed on system generated reports
Normal State: Selects the normal contact state of the wired device.
Logic Enable Group: Another form of AND gate where all input in the same logic group are a member
of the same gate.
Delay Time: Delay the TMS reaction to the input.
Apply To Input Going: Selects whether the TMS response is delayed with the input going active or
inactive.