OPERATION MANUAL TMS4000
TMS4000 Operation Manual 2018-08-03.docx August 3, 2018
PAGE 49
Sensor Input Configuration settings. See below for a description of each setting.
Enable: Enables the sensor as either Alarm to generate an alarm on the TMS or as Relay to control
a relay in the TMS without an alarm. Choosing alarm does not prevent you from also activating a
relay on this condition.
Type: Enter the model number of the sensor connected to the TMS.
Name: Choose from the list of predefined names or type in a 16 character name.
Tag: Printed on system generated reports.
Associate Sensor With: Helps to locate a sensor by associating it with a tank or dispenser.
Normal State: Selects the normal contact state of the sensor, open or closed.
Mode: Select Leak for sensor detecting leaks. Select Other for sensor used for purposes other than
leak detection. The integrated horn beeping pattern will differ for sensors defined as Leak sensors
versus Other sensors.
Fault Detect: Must be selected for sensors with integrated fault detection circuitry.