POWER ELECTRONICS
MECHANICAL INSTALLATION
29
It is recommended to construct a cable duct below the middle part of the cabinet. The duct width
may not exceed 300 mm and the contact surface of the floor must resist the cabinet weight that lies
on the legs.
5.3. Clearances
The SD700 VFD must be installed in vertical position, and firmly fastened through the dedicated
anchorages placed in the rear part of the drive that avoid any movement.
If the equipment is installed inside a cabinet, ensure that the hot air expelled from the VFD is evacuated
outside. This hot air can be aspirated again so the drive may suffer from overheating. To ensure a suitable
cooling avoid the recirculation of air and keep the minimum clearance distances indicated below.
Figure 5.3 Minimum clearances for frames 1 to 4
Figure 5.4 Minimum clearances for frames 5 to 11
FRAME
DISTANCE (mm)
FRONT
CLEARANCE
A
B
1
200
200
700
2
200
200
800
3
200
200
800
4
300
300
820
FRAME
DISTANCE
(mm)
FRONT
CLEARANCE
A
5
400
930
6
400
940
7
400
1260
8
400
1260
9
400
940
10
400
1260
11
400
1260