42
Powerware 9315 (100 kVA--160 kVA) Installation
164200292 REV. E 041500
TB1
TB2
(ON COMMUNICATIONS
PANEL OF THE UPS)
D E --- 9 C O N N E C T O R
Figure 22. Wiring an RMP to the UPS
4. Connect RMP wiring to the terminal block using terminations shown in Table E.
Tab l e E . R M P W ire Termin at i on s
From RMP A To UPS Remarks
T B 1 --- 4
T B 3 --- 1
T B 1 --- 5
T B 3 --- 2
TWISTED WIRES (4)
1 --- 2 T U R N S P E R
T B 1 --- 6
T B 3 --- 3
3INCHES
T B 1 --- 7
T B 3 --- 4
From RMP B (if used) To UPS Remarks
T B 1 --- 4
T B 3 --- 5
T B 1 --- 5
T B 3 --- 6
TWISTED WIRES (4)
1 --- 2 T U R N S P E R
T B 1 --- 6
T B 3 --- 7
3INCHES
T B 1 --- 7
T B 3 --- 8