9116 - Product Version 9116-003 11
Sensor error current:
when detecting ............................................... Nom. 2 μA
else ....................................................................... 0 μA
Current input:
Measurement range ................................................ 0...20 mA
Programmable measurement ranges ............... 0...20 and 4...20 mA
Input resistance........................................................ Nom. 20 Ω + PTC 50 Ω
Sensor error detection:
Loop break 4...20 mA .................................... Yes
NB: Only when input is selected as 4...20 mA
Voltage input:
Measurement range ................................................ 0...10 VDC
Programmable measurement ranges ............... 0...1 / 0.2...1 / 0...5 / 1...5 /
0...10 and 2...10 VDC
Input resistance........................................................ Nom. >10 MΩ
Current output:
Signal range (span) ................................................. 0...20 mA
Programmable signal ranges ............................... 0...20 / 4...20 /
20...0 and 20...4 mA
Load (max.) ................................................................. 20 mA / 600 Ω / 12 VDC
Load stability ............................................................. 0.01% of span / 100 Ω
Sensor error reaction.............................................. 0 / 3.5 / 23 mA / none
NAMUR NE 43 Upscale / Downscale ................. 23 mA / 3.5 mA
Output limitation:
on 4...20 and 20...4 mA signals ................ 3.8...20.5 mA
on 0...20 and 20...0 mA signals .............. 0...20.5 mA
Current limit ............................................................... 28 mA
2-wire 4...20 mA output:
Signal range ............................................................... 4...20 mA
Load stability ............................................................. 0.01% of span / 100 Ω
Load resistance......................................................... ≤ (Vsupply -3.5) / 0.023 A [Ω]
External 2-wire supply range ............................. 3.5...26 VDC
Effect of external 2-wire supply
voltage variation ...................................................... <0.005%ofspan/V
Relay output in safe area:
Relay functions ......................................................... Setpoint, Window, Sensor error,
Power and Off
Hysteresis, in % of span / display range ........ 0.1...25 / 1...25
On and Off delay ...................................................... 0...3600 s
Sensor error reaction.............................................. Break / Make / Hold
Max. voltage .............................................................. 250 VAC / 30 VDC
Max. current ............................................................... 2 AAC / 2 ADC
Max. AC power .......................................................... 500 VA / 60 W