ProfiHub B5+ / B5+RD User Manual
_______________________________________________
Version 2.0 – July 2014 Page 34 / 56
ProfiHub-B5-Plus-Manual-EN.docx © PROCENTEC 2014 - Copyright - all rights reserved
3.3.7 Changing the Diagnostics duration/timeout
You can change the duration of the Extended Diagnostics warning in steps of 100 milliseconds. The
default value is 10, so 1 second. The maximum value is 255.
3.3.8 Changing the Device Lost timeout
The Diagnostics Device waits for a certain time before it considers a slave to be lost. This works in a
similar way as the ProfiTrace Live List, where the background turns yellow when a slave stops
communicating. This timeout can be changed in steps of 1 second. Default value is 5, and maximum
value is 255.