Technical Data ProfiHub B5+ and B5+RD
PROFIBUS Diagnostics Device specifications (only for B5+RD)
Supported protocol
Ident Number
GSD filename
Bus address
Transmission speed
Transmission speed detection
Maximum transferrable data
DP-V0
6970
PROC6970.gsd
0-126 (software address only, set by software)
9.6 kbps .. 12 Mbps (including 45.45 kbps)
Auto Detect
85 bytes input and 5 bytes output
PROFIBUS cable specifications
Cable lengths
Cable thickness
Wire diameter
Wire type
Number of devices
Termination
Cascading depth
Redundancy
1200 m at 9.6 kbps to 93.75 kbps
1000 m at 187.5 kbps
400 m at 500 kbps
200 m at 1.5 Mbps
100 m at 3 Mbps to 12 Mbps
10 mm (when the ground rail is used)
< 2.5 mm
2
Stranded or Solid core
Maximum 31 per Channel (including ProfiHubs, OLMs,
Laptops/PCs, etc)
Integrated and switchable.
Powered according to IEC 61158 (390/220/390 Ohms)
- All Channels (default on)
- Main-Channel (default off)
No limits
Yes
Power supply specifications
Power supply voltage
Redundant power supply
Current consumption
Power dissipation
Reverse polarity protection
Cable thickness
Wire diameter
9 to 31 VDC
Yes
130 mA at 24 V power supply (all Channels fully loaded)
Max. 4.1 W
Yes
10 mm (when the ground rail is used)
< 2.5 mm
2
Alarm contact
Voltage
Current
Max. 24 VDC
0.5 A
Others
MTBF T.b.d.