7 PROFIBUS DP Extensions
Bit Position
Byte
7 6 5 4 3 2 1 0
Designation
0
Structured_Length
1 0 0 0 0 0 1 1 1 Structure_Type
2 0 0 0 0 0 0 0 0 Slot_Number
3 0 0 0 0 0 0 0 0 Reserved
4 0 0 0 0 0 0 0 1 Version
5 Publisher_Addr
6 Publisher_Length
7 Sample_Offset
8 Dest_Slot_Number
9 Offset_Data_Area
10 Sample_Length
11
:
120
further link entries
Figure 7-9: Format of the Structured_Prm_Data with DXB Subscribertable
(specific link is grey scaled)
The user must copy the link entries of DXB Linktable or DXB
Subscribertable, without Dest_Slot_Number and Offset_Data_Area, in the
DXB_Link_Buf and set R_Len_DXB_Link_Buf. Also the user must enter the
default status message in DXB_Status_Buf with the received links and
write the appropriate values to R_Len_DXB_Status_Buf. After that, the
parameterization interrupt can be acknowledged.
60 Revision 1.03
VPC3+C
User Manual
Copyright © profichip GmbH 2004-2006