EasyManua.ls Logo

Prolon VC2000 Series - Page 85

Default Icon
98 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.5.1 - Unit with Cooling Stages (On-O)
Set the Control Mode to “Demand”.
Select how many cooling stages in the “Mechanical Cooling” dropdown list (up to 4x stages).
OFF ON
Setpoint
Dierential
Demand
OFF ON
Setpoint
25% 45%
35%
20%
Dierential
Demand
• Thesetpointanddierentialvaluesdeterminewhenthecoolingstageturnson,andwhenitturnso.Thedierentialis
centered on the setpoint.
• LookingatStage1,withasetpointof35%andadierentialof20%.
Stage 1 will be activated once the demand (source: Math 1) reaches the following point:
Stage 1 On = Setpoint + 1/2 (Dierential)
Stage 1 On = 35% + 1/2 (20%) = 45%
When Stage 1 is activated, the unit will supply cool air to the zones.
All VAV zones with a cooling demand will open their dampers. All zones with a heating demand will close their dampers to
their minimal positions (unless duct heater reheat has been enabled).
• Asthezonesreceivecoolair,theirindividualcoolingdemandswilldecrease,thusdirectlyaectingMath1.Asaresult,
Math 1 will decrease.
Stage 1 will be deactivated once the demand (source: Math 1) reaches the following point:
Stage 1 O = Setpoint - 1/2 (Dierential)
Stage 1 O = 35% - 1/2 (20%) = 25%
• Congureadditionalcoolingstagesasneededusingthesameguidelines.
9-6

Related product manuals