93-530-70 Issue 0 Page 20 of 44 © Protec Fire Detection PLC 2007
14.0 Programming Details
In general the front panel buttons have the following alternate functions when the 3300 is in
programming mode.
When Access Level 3 programming functions are being performed the ‘Supply Present’ indicator will
flash.
Button 1 Toggle.
Button 2 Scroll.
Button 3 Accept.
Button 4 Back / Exit / Program.
14.1 Programming Zone Disablements
The 3300 can have one, or more, of its detector zones disabled. When a zone is disabled faults and
activations from that zone are inhibited.
1. From access level 1 enter your 5 digit user code 1 3 4 4 2 or turn the key-switch (depending on
the model purchased).
2. The ‘level 2 Accessed’ indicator will illuminate.
3. Press button 2 once – The ‘General Disablement’ indicator will illuminate steady to show the zone
disablement option is selected (the normal front panel display is temporarily replaced with the
programming display). Any current disablements will be displayed on row 1 of the display. Accept
the option by pressing button 3.
4. The ‘General Disablement’ indicator will flash, showing this option has been accepted.
5. Highlight the zone to be disabled by repeatedly pressing button 2.
6. Press button 1 to show that it is to be disabled / not disabled. The relevant row 1 indicator will be
illuminated if the zone is disabled.
7. Follow the procedure above until all zones that are to be disabled have their row 1 indicators
illuminated.
8. Press button 3 to return to the programming selection menu.
9. Press button 4 to accept and program the disablement set-up and return to access level 2.
10. The yellow ‘General Disablement’ indicator will be illuminated steady, as will the row 2
disablement indicator for the relevant zone(s).