16.0 Disabling The Fire Link Interface
It is possible for the authorised user (at access Level 2 or 3) to disable the Fire Link interface (if fitted).
Disabling the interface inhibits Fire Link faults and activations.
1. From access level 1 enter the 5 digit engineer code 1 3 4 2 4. The ‘Supply Present’ indicator
will flash indicating level 3 has been accessed and all programming features are available.
2. Using button 2 scroll to the ‘Alarm Outputs’ indication. Any current settings in this option will be
displayed on row 1 of the display, on zone 4. Accept this option by pressing button 3.
3. The ‘Alarm Outputs’ indicator will flash, showing this option has been accepted.
4. Select the ‘Disable Fire Link’ option by pressing button 2 until the row 2 indicator for zone 4 is
llluminated
5. Press button 1 to show that the fire link is to be disabled / not disabled. The row 1 zone 4 indicator
will be illuminated if the fire link is disabled.
6. Press button 3 to return to the selection menu.
7. Press button 4 to accept and program the set-up and return to access level 2.
8. The ‘Fire Link’ and ‘General Disablement’ indicators will be illuminated.