15.0 Overriding System Delays
It is possible for the authorised user (at access Level 2 or 3) to override any delays (zonal or fire link)
that may have been set up at access level 3. The procedure to do this is as follows.
1. From access level 1 enter your 5 digit user code 1 3 4 4 2 or turn the key-switch (depending on
the model purchased).
2. The ‘Level 2 Accessed’ indicator will illuminate.
3. Using button 2 scroll to the ‘Alarm Outputs’ indication. Any current setting in this option will be
displayed on row 1 of the display, on zone 3. Accept this option by pressing button 3.
4. The ‘Alarm Outputs’ indicator will flash, showing this option has been accepted.
5. Select the delay override option by pressing button 2 until the row 2 indicator for zone 3 is
illuminated.
6. Press button 1 to show that delays are no be overridden / not overridden. The row 1 zone 3
indicator will be illuminated if delays are overridden.
7. Press button 3 to return to the selection menu.
8. Press button 4 to accept and program the set-up and return to access level 2.
9. The ‘Output Delay’ indicator will be extinguished. All delays (zonal and fire link) are now
overridden.