93-530-70 Issue 0 Page 39 of 44 © Protec Fire Detection PLC 2007
29.0 3300 Features Specification
Delay to Zone Activation 0 to 10 minutes programmable (applies to all zones programmed for delay)
Coincidence on Zones 2 or more zones programmable (2 or more zones must activate together to trigger
panel). A default time-out is given if only one coincidence zone activates. The time-out
is the same as the one programmed for zone delays.
A manual activation on a coincidence zone will also activate the panel.
Non-latching Zones 1 or more zones may be programmed non-latching. Panel resets when cause of the fire
is cleared. Global fire and fire link outputs (if fitted) do not activate.
Zone Disablements 1 or more zones can be disabled to prevent faults and activations
Alarm Disablements Alarm Circuits 1 / 2 and 3 / 4 can be disabled to prevent faults and activations.
Fire Link Disablement The fire link PCB (if fitted) can be disabled to prevent faults and activations.
Fire Link Delay The fire link PCB (if fitted) can be set to have an activation delay.
Zonal Test 1 or more zones. When triggered operates alarm outputs for 4 seconds, then resets
panel (assuming no other non-test zone are activated)
Ability to Distinguish Between When the Manual Call Point Incorporates a 180Ω resistor.
Manual or Automatic Zone Activation
Ability to re-activate a silenced zone A zone activated by an automatic detector, then silenced, can be
by a manual Call Point Activation re-triggered by a Manual Call Point Activation.
Ability to Accept Repeat Panels Up to eight 3300 Repeat Panels may be connected on the external expansion port to
provide full main panel display mimic and allow access to all level 2 functions from
remote parts of a site. No extra drivers are required to run the repeat panels.
Ability to Accept a Fire Link One Fire Link Interface may be connected to the internal
Interface expansion port.
Peripheral Interfaces Available 8 way zonal fire / fault Volt free contact Interface, connects to the internal
expansion port.
Fault Diagnosis Comprehensive fault diagnosis features can be accessed at level 3.
These give further details of PSU faults, Zone Faults, Alarm Faults, System
Faults, Fire Link faults.
Note: Due to a policy of continuous improvement Protec Fire Detection PLC reserve the right to alter the specification without
prior notice.