Communication
error between
master and slave
BMS
Bit17
Comm. and
hardware
1. Battery string(s)
over-discharged
2. BMS CMU error
Self-test module
coulomb error
Bit15
Self-test Self-test failed
Self-test module
Initial Error
Bit16
Self-test Self-test failed
1. Restart
2.If problem remain, contact Pylontech
service engineer.
Self-test module
detecting
amount error
Bit14
Self-test Self-test failed
Emergency stop
Bit13
External
Command by external
device via dry
contactor
Command by external device, not an
error actively report by Battery system.
contact Pylontech service engineer.
1. Check whether the battery string(s)
has been overdischarged or not via
multimeter.
2. Check the comm. cables between
master and slave BMS, make sure the
cable is 8PIN pin – pin CAT5 Ethernet
cable. If BMS and MBMS is communica-
tion via CANBUS (no Ethernet switch),
make sure the CANBUS physical length
is less than 12m. Restart the system.
3. Reverse sequence connect the
comm. cable between the BMSs and
change the ADD address settings.
Restart the system.
4. Change the BMS CMU or BMS.
5. If problem remain, contact Pylontech
service engineer.
contact Pylontech service engineer.
Safety check
failureBit11
Self-test
Chip self-test failed
1.Restart
2.If problem remain, contact Pylontech
service engineer.
Self-test volt error
Bit10
Self-test
Battery cell voltage
measurement
mismatch with
DCBUS voltage
measurement
Failure Definition SolutionPossible ReasonFailure Type
1.Restart
2.Check the connectivity and reliability
of the power and comm. cable by
reconnection.
3. Swap the current measurement
board or BMS
4.If problem remain, contact Pylontech
service engineer.