31
2
resistance needs
to be activated ON
(upward) at the
first(master
control) and last
node(the last
slave control),
when multiple
controllers are
connected in
parallel.
Slave
3
Slave
4
Slave
5
Slave
6
Slave
7
Slave
The ADD of each control module must be set different, setting it
to the same will indicate a fault. The address range must be set
to 1-7, other addresses will not be recognized.
Note
When both V1 and V2 versions of the control module are present in
the BESS, the V2 version of the control module must be the master.