Some system function must be maintenance during the EMS restart, it
is recommended to maintenance the system every 6 months.
5.3.8. Recycle
Note
Damaged batteries may leak electrolyte or produce flammable gas.
In case a damaged battery needs recycling, it shall follow the local
recycling regulation (i.e. Regulation (EC) Nº 1013/2006 among European
Union) to process, and using the best available techniques to achieve
a relevant recycling efficiency.
6. Remarks
6.1. Storage
For long-term storage (more than 3 months), the battery cells should
be stored in the temperature range of 5~45, relative humidity <65%
and contains no corrosive gas environment.
The battery module should be shelfed in range of 5~45, dry, clean
and well ventilated environment. Before storage the battery should
be charged to 50~55% SoC;
It is recommended to active the chemical (discharge and charge) of
the battery every 3 months, and the longest discharge and charge
interval shall not exceed 6 months.