Page: 42
B-01 (xx)
WLs LOW BATT
Low battery on wireless siren
number ‘xx’
Replace the battery on the radio siren
mentioned.
I-01 (xx)
WLs SUPERVN
Device on wireless input number ‘xx’
has not ‘checked in’
Perform a walk test on the detector, and a
diagnostic signal strength test and then try
replacing the battery.
B-01 (xx)
WLs SUPERVN
Wireless siren number ‘xx’ has not
‘checked in’ within 20 minutes time
Test the siren, perform wireless signal
strength diagnostic. Consider replacing the
battery or relocating the siren.
- 01 (xx)
CASE TAMPER
Tamper fault on input number 01
‘xx’ = any input number
Check the tamper switch on the detector and
make sure the case is closed properly.
WLs TAMPER Bxx Tamper fault on wireless siren
number ‘xx’
Check the tamper switch on the radio siren
mentioned.
WLs JAMMING Pnl
Jamming fault on the Enforcer
HomeControl+ Panel
Check no radio interference is in close
proximity to the radio devices/panel.
WLs Supervn Fault No ‘supervision polls’ were received
for 20 minutes before the setting
operation. Wireless Input or Bell
input number will be shown so the
problem is easily identified
Test the signal strength/battery on each of
the wireless devices.
Input (xx)
Wirles Poll Fail
Wireless Poll Fail displays when no
‘polls’ (wireless comms) are received
for 20 minutes before the set
operation.
Test signal strength / battery status for each
wireless device (especially the one that
corresponds to the input named by the fault
message).
WLs Input /
Input Type
Mismatch
Wireless devices are learned on
inputs but no input types have been
programmed for them.
Program the input type for each of the
wireless devices learned in the CHANGE
INPUTS.
9.2.7 Errors When Setting
Fault Description Solution
Please leave via
exit door
If the exit mode is programmed as
Final Door, then the premises must
be left through this door for the
system to be set.
Leave via the agreed exit route.
Exit Via… If any follow detectors or door
contacts are open during the setting
procedure, a prompt will be
displayed to close them.
Close all inputs.
Unable To Set A fault condition exists on the
system. Details of the fault will scroll
on the display.
Correct the problem if it is an input which is
open, or call an engineer.
Alarm during the
setting
Fail to set time has been exceeded. Leave the premises within the fail to set
time, increase the fail to set time in ‘timers’
or disable this feature in system options.
Alarm during the
setting procedure
Instant inputs have been activated. During the setting procedure do not activate
‘instant inputs’.