SECTION 7 - OPERATION
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
Communication Ports
The 03478 microboard has the following native
communication ports.
TB3 Port 1 Native BAS RS-485.
SW1 RS-485 Biasing Switch for Port. Set to ON if
Chiller is in an End Of Line position on the network.
U26 is the Port 1 RS-485 Driver Chip. It is
socketed to allow field replacement. RX1 and TX1
LEDs illuminate to indicate Port 1 communications
activity.
BUILDING AUTOMATION SYSTEM (BAS)
COMMUNICATIONS
There are three different ways the chiller communi-
cates to the BAS.
Via board Native Communication protocol
Using an E-Link Gateway
Using an SC-EQ Communication Card
Using Communications Protocol
TB3 Port 1 Native BAS RS-485.
SW1 RS-485 Biasing Switch for Port. Set to ON if
chiller is in an End of Line position on the network.
U26 is the Port 1 RS-485 Driver Chip. It is sock-
eted to allow field replacement. RX1 and TX1 LEDs
illuminate to indicate Port 1 communications activity.
QTC4 Native Communication Setup
Native communication is applicable to three types of
protocols, they are BACnet, N2 and Modbus RTU.
It requires IPU II Microboard (331-03478-101) and
software version Y.ACS.20.02 or later.
BACnet MS/TP Setup Port 1 (TB3)
To setup the BACNET MS/TP Port 1, follow the steps
below:
1. Connect the BACnet MS/TP Network to Port 1 on
the IPU II I/O Board.
2. Set up the QTC4 Port 1 (P1) for BACnet
Communications as shown in Figure 18 on Page
99.
To access the Port communication parameters:
1. Press the PROGRAM key once.
2. Enter password 5255.
3. Press the (ENTER) key to display the Port 1
(P1) settings.
Set the following parameters:
1. DE Modier Address (number entered is
multiplied by 100): set as required by network.
2. DE Modier Offset (number entered is added to
DE Modier Address): set as required by net-
work (see NOTE below).
3. P1 Protocol: set to BACNET (Default Setting).
4. P1 Manual MAC Address: set to 1
(Default Setting).
5. P1 Baud rate: set as required by network.
If not known, set to AUTO.
6. P1 Parity: set to NONE (Default Setting).
7. P1 Stop Bits: set to 1 (Default Setting).
The BACnet DE Instance (Device Instance) is
determined by adding the [DE MODIFIER AD-
DRESS x 100] with the DE MODIFIER OFFSET. For
example, if the desired DE Instance address is 5023,
set the DE Modifier Address to 50, and then set the
DE Modifier Offset to 23 (50 X 100 + 23 = 5023).
DE Instances must be limited to values between
1 and 4,194,303 and every device in the network must
have a unique device Instance.
N2 Metasys Setup Port 1 (TB3)
1. Connect the N2 Network to Port 1 on the IPU II
I/O Board as shown in Figure 18 on Page 99.
2. Set up the QTC4 Port 1 (P1) for N2 Communica-
tions.
To access the Communication parameters:
You must always cycle power to the
microboard following port setting
changes.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Quantech QTC4 STYLE A Series and is the answer not in the manual?

Quantech QTC4 STYLE A Series Specifications

General IconGeneral
BrandQuantech
ModelQTC4 STYLE A Series
CategoryChiller
LanguageEnglish

Related product manuals